26
SXL-EX
Operation, Installation, and Maintenance Manual
TABLE 4
ELECTRICAL REQUIREMENTS FOR BATTERY CALCULATIONS
AND POWER MANAGEMENT
Standby
Current
Alarm
Current
Main Board Current
0.110A
0.120A
IDC Current (Zones 1-4):
Number of IDC Zones
________ 0.009A (Standby) =
________ 0.120A (Alarm) =
_______A
0A
0A
______A
NAC Device Current: Current <=1.5A per NAC
NAC 1 ________ See Note 1
NAC 2 ________
0A
0A
______A
______A
Auxiliary Port Current: Current <= 0.5A
SRC-8 Module See Note 1
Standby Current 0.018A
Alarm Current 0.018A
Number of Programmed Relays
________ x 0.026A =
______A
0A
______A
______A
SZE-4X Module Standby Current 0.006A
Alarm Current 0.006A
Number of Programmed Relays
________ x 0.026A =
IDC Current (Zones 5-8):
Number of IDC Zones
________ x 0.009A (Standby) =
________ x 0.120A (Alarm) =
______A
0A
______A
0A
______A
______A
0A
______A
SZE-8AX Module Standby Current 0.006A
Alarm Current 0.006A
IDC Current (Zones 5-8):
Number of IDC Zones
________ x 0.009A (Standby) =
________ x 0.120A (Alarm) =
______A
_____A
0A
______A
0A
______A
LED-3/4 Module
Number of LED-3/4 Modules
________ x 0.010A (Standby) =
________ x 0.042A (Alarm) =
______A
0A
0A
______A
SLT-1 Module
Standby =
Alarm =
0.050A
0A
0A
0.345A
Total
______A
______A
Total Standby Current Standby Hours (24, 48, or 60) Standby A-H Current
___________ x __________________ = ______________A-H
Total Alarm Current A-H Multiplier Factor (5 Min.) Alarm A-H Current
___________ x 0.083 = ______________A-H
(Standby A-H C Alarm A-H Current) x 1.22 =
Minimum A-H Battery Size
______________A-H
<= means less than or equal to
NOTES:
1. In addition to deter-
mining the required
battery size, consider-
ation must be given to
the overall current
drawn by the system.
The total system
current capability is
3.5 amps at 24 volts.
The total alarm current
must not exceed 3.5
amps for any combi-
nation of the basic
system plus any
additional modules
used. When installing
additional modules,
the current available
for the NAC circuits
and auxiliary port must
be derated to keep the
total alarm current
below 3.5 amps.
2. For NFPA 72 Remote
Station connections,
provide 60 hour
battery backup.