Installing the Control Panel
Remove all system power before
installation, first battery and then AC.
(To power up, connect the
AC first, then the battery.)
All wiring must comply with
national and local codes
.
Install the SXL-EX control panel by following
the steps listed below.
1.Install the enclosure.
Fasten the
enclosure securely to a clean, dry, shock
and vibration free surface. Consider the
following placement factors when
mounting the enclosure: height as it
relates to the front panel, weight and size
of the enclosure, and local mounting
codes. Refer to the
EN-SX Installation
and Power Limited Wiring Instructions,
P/N 315-095994, for further information.
Figure 4
Transformer Mounting
2.Fasten the power transformer to the
inside of the enclosure.
Mount the
transformer on the four studs in the upper
left-hand corner of the EN-SX enclosure,
as shown in Figure 4, using the hardware
provided.
3.Pull all field wiring into the enclosure.
Dress the wiring to the approximate
location to which it will go on the SXL-X
Main board.
4.Install the PC Board mounting metal
hex standoffs and plastic spacers.
Mount the six PC Board metal hex stand-
offs and two plastic round spacers, as
shown in Figure 5.
5.Install the Main board.
Mount the Main
board to the standoffs in the center of the
enclosure (Refer to Figure 6).
a. Fasten two of the six screws provided
in the PC board mounting hardware in
the two bottom metal hex standoffs
Figure 5
Mounting the Standoffs and Spacers
Technical Manuals Online! - http://www.tech-man.com