3
SXL-EX Operation, Installation, and Maintenance Manual
CODE
DESCRIPTION
1
AC power fail
2
NAC 1 trouble
3
NAC 2 trouble
4
Ground fault
5
Municipal tie fault
6
Battery fault
7
System Configuration fault
8
Auxiliary port fault
9
Outputs bypassed
0
Hardware failure
E
Enter password
A
Password accepted
F
Password fail
P
Program mode
t
Test mode
L
Leave Program/Test mode
The Function Keys
The ACK key
is used to acknowledge alarms,
troubles, and supervisory conditions. In general
the LEDs change from pulsing to steady to
indicate that the condition was acknowledged.
The SILENCE key
silences the notification
appliance circuits that are configured as
silenceable. Pressing the SILENCE key a
second time causes the NACs to re-sound.
The RESET key
resets the SXL and all of the
smoke detectors.
The DRILL key
activates all of the notification
appliance circuits.
The yellow zone status LEDs
indicate
a trouble or supervisory condition existing on a
particular input. Pulsing indicates the condition
was not acknowledged; on steady indicates it
was acknowledged.
The red zone status LEDs
provide an
indication of the status of a particular zone.
Pulsing indicates an alarm condition in that
zone. When the alarm is acknowledged, the LED
remains on steady until the panel is reset.
FRONT PANEL FUNCTIONS
The front panel of the SXL-EX is comprised of
a seven segment display, function keys, and
LEDs. Their functions are described below
(Refer to Figure 2):
The LEDs
The green
Power LED
remains on steady when
AC power is connected and pulses when the unit
is operating from batteries.
The red
Alarm LED
pulses when an alarm is
detected until it is acknowledged. Then it remains
on steady until the alarm condition is reset.
The yellow
Supervisory LED
pulses when a
supervisory condition is detected until it is ac-
knowledged. Then it remains on steady until the
supervisory condition is reset. Note that the
pulsing rates of the trouble and supervisory
conditions are different.
The yellow
Trouble LED
pulses when a trouble
condition is detected until it is acknowledged.
Then it remains on steady until the trouble condi-
tion is reset. Note that the pulsing rates of the
trouble and supervisory conditions are different.
The yellow
Bypass/Alarm Silence LED
is on
steady when a zone in the system is bypassed
and it pulses when a notification circuit is silenced.
When an initiating device zone is bypassed, the
appropriate yellow zone trouble LED is on.
The
Test/Program LED
is on steady when the
Test mode is selected and it pulses when the
Program mode is selected.
The Sounder
CONDITION
RATE OF PULSATION
SYSTEM ALARM
Sounds steady
TROUBLE
Pulses at 50% duty cycle
SUPERVISORY
Pulses at 25% duty cycle
CPU FAILURE
Pulses once every 2 seconds
The seven segment display
indicates
the various system troubles and the programming
and test modes. The numbers and symbols that
appear on this display are described in the
following chart.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com