10
SXL-EX
Operation, Installation, and Maintenance Manual
To Acknowledge Alarms
1. Unlock and open the door.
2. Press
ACK
to acknowledge (Block
Acknowledge)
all
alarms and other
conditions. The system
ALARM
and the
Zone ALARM
LEDs on the front panel
stop flashing and remain on. The
systems internal audible silences.
To Silence The Notification Appliance
Circuits
Press
SILENCE
after all alarms are acknowl-
edged. The
BYPASS
LED on the front panel
flashes. The following four conditions are
checked before the Notification Appliance
Circuit(s) can be silenced:
1. If either NAC is programmed as
NON-
SILENCEABLE
, it will not silence.
2. If the NAC inhibit timer has been pro-
grammed (see
Set System Timing
on
page 13), the NAC will not silence until
the inhibit time delay has expired (6
seconds to 5 minutes.)
3. If either NAC is programmed for temporal
coding, it will complete sending out
the entire current temporal round before
silencing.
4. If either NAC is programmed for
ZONE
CODING, all
coded rounds for
each
zone
in alarm must be sent out before the NAC
will silence.
Once the NACs have silenced, pressing the
SILENCE
a second time causes the Notifica-
tion Appliance Circuits to re-sound, and the
BYPASS
LED to turn off.
To Reset
Press
RESET
. (The system will not reset until
all alarms, supervisories, and troubles are
acknowledged and all conditions are returned
to normal.)
Responding to a Supervisory
Condition
How the System Annunciates
Supervisories
When a supervisory condition is detected, the
system causes the
SUPERVISORY
LED and
one of the yellow
Zone TROUBLE
LEDs on
the front panel to flash and the systems
internal audible to sound.
To Acknowledge Supervisories
1. Unlock and open the door.
2. Press
ACK
to acknowledge (Block
Acknowledge)
all
supervisory and other
conditions. The system
SUPERVISORY
and the
Zone TROUBLE
LEDs on the
front panel stop flashing and remain on
and the systems internal audible silences.
To Reset
Press
RESET
. (The system will not reset until
all alarms, supervisories, and troubles are
acknowledged and all conditions are returned
to normal.)
Responding to a Trouble Condition
How the System Annunciates Troubles
When a trouble is detected, the system
causes the
TROUBLE
LED and the appropri-
ate yellow
Zone TROUBLE
LEDs on the
front panel to flash and the systems internal
audible to sound. Troubles will clear prior to
Acknowledge if the condition which caused
the trouble returns to normal.
Note:
Exceptions are Class A zone troubles
which always latch.
System troubles are also annunciated by the
appropriate trouble code in the 7-segment