SXL-EX Operation, Installation, and Maintenance Manual
Last Event Record
(Test Level 4)
This feature records the zone in which the
last event occurred in each of four catego-
ries: Alarms, Troubles, Verified Alarms, and
Supervisories. This can be used for trouble-
shooting one-time reports of events.
Program Mode
The program mode allows the user to change
the configuration of the SXL-EX system. The
program mode has
nine
levels. Each level
allows the user to configure a different func-
tion within the SXL-EX.
When the program mode is enabled, the
current programming levels and sublevels
display in turn on the seven segment display.
The order of the display is as follows:
1. the program level is displayed first
2. then a hyphen (-) is displayed
3. then the sublevel is displayed
4. then the display is blank.
The entire sequence then repeats.
In the programming mode, the four function
keys operate differently than they do in the
normal mode. Their functions are as follows:
The Acknowledge key
toggles between the
T
est mode, the
P
rogram mode, and the
L
eave mode. The seven segment display
shows
t, P,
and
L,
respectively, to indicate
these modes.
The Reset key
is used to select program
levels and options inside the programming
levels.
The Drill key
selects options and toggles
options on and off.
The Silence key
selects different sublevels.
Pressing silence when the seven segment
display shows
L
exits the user from the
program/test mode.
PROGRAM LEVEL DESCRIPTIONS
Level 1:
Bypass or enable the SZE-4X or
SZE-8AX Zone Expander card.
Level 2:
Bypass or enable the Relay and/or
the Open Collector Outputs on the
optional SZE-4X, or SZE-8AX and
SRC-8 cards.
Level 3:
Allows configuration of the Initiat-
ing Zone Circuits to any one of the
following types:
Initiating, Veri-
fied Initiating, Supervisory,
and
Generic Input.
Level 4:
Allows configuration of the Notifi-
cation Appliance Circuits to Non-
Silenceable and any one of the
following types:
Steady, Tempo-
ral, March Time,
and
Simplified
Zone Code.
Level 5:
Allows programming of the out-
puts on the optional SZE-4X or
SZE-8AX Zone/Output Expander
card and the SRC-8 Relay card to
follow Alarms on the Initiating
Zone Circuits.
Level 6:
Allows programming of timer and
counter values:
the Verification Timer between
15 and 50 seconds.
the Inhibit and Cutoff Timers
of the Notification Appliance
Circuits.
the Round Count ranging from
3 to 8 for Simplified Zone Coding.
Level 7:
Allows programming of the 4-digit
Password.
Level 8:
Allows programming of the AC
Fail Trouble Signal Delay.
Level 9:
Enable/Disable the SRC-8;
LED-3/4, Addresses 1 and 2;
SLT-1; and SZE-4X/SZE-8AX.