Messages and Diagnostics
SIWAREX FTA
7-142
Error
No.
Data and
command errors -
description
Solution
35-
42
Interface
parameter error
35
Baud rate not
permitted for
RS232
The baud rate for the RS232 interface is not permitted. Define
the baud rate.
36
Process alarm
assignment or
process value
assignment
implausible
The assignment of the process alarm or the process values in
DR7 for the S7 interface is incorrect. Change your assignment.
37
Baud rate not
defined for RS485
The baud rate for the RS485 interface is not defined. Define the
baud rate.
38
Reserved
39
Reserved
40
Reserved
41
Reserved
42
Reserved
43-
50
Trace not possible
43
Trace task not
possible since
MMC full
44
Trace task cannot
be executed, since
MMC is defective or
non-existent
45
Trace recording
cycle too small
The trace cycle in DR7 is too short. Define parameters for
a longer trace cycle (for MMC minimum 5 x 10 msec).
46
Reserved
47
Reserved
48
Reserved
49
Reserved
50
Reserved
51
Reserved
51
Reserved
52
Reserved
53
Reserved
54
Reserved
55
Reserved
56-
62
Log text not
plausible
56
Log text too long
The log text with the fill parameters is too long of the end
character (EOT) is missing. Change the log text.
Ensure that the proper number of characters for the
corresponding field are used in place of the respective print field
code. The overall length of the text filled with values may not
exceed 160 characters (including printer control character but not
the terminating EOT).
57
Log text contains
fields that are not
permitted
Log text contains fields that are not permitted Change the log
text.