Functions
8.17 Diagnostics functions
SITRANS TR200/TR300
Operating Instructions, 04/2007, A5E01071992-01
51
8.17
Diagnostics functions
The diagnostic concept of the SITRANS TR200 and the SITRANS TR300 envisages that a
diagnostic warning can be set in the parameters for diagnostic functions that are used for
monitoring limit values. A diagnostic interrupt can be set in the parameters for diagnostic
functions that are used for monitoring error conditions.
Diagnostic interrupts are output via:
●
Analog output
●
Operating indicator (LED)
●
Only for SITRANS TR300: HART communication
Diagnostic warnings are output via:
●
Only for SITRANS TR300: HART communication
Diagnostic interrupt:The device goes into the alarm current state. In addition, the diagnostic
event is made available via the operating software. The following table summarizes all the
diagnostic functions that can be set in the parameters. If multiple errors occur
simultaneously, the priority settings apply. Priority 1 is the highest priority.
Diagnostic warning: The device transmits the diagnostic event that has occurred via the
operating software. The analog output value is unchanged.
Diagnostic function
Priority
HART
(only for
TR300)
Analog output LED
Diagnostic interrupt
Hardware/firmware defect
•
RAM/ROM error
•
Flash/EEPROM error
•
Watchdog error
•
Electronics defect
(hardware/firmware)
1
1
1
1
Status
Status
Status
Status
On alarm
value
On alarm
value
On alarm
value
On alarm
value
Red
Red
Red
Red
Electronics temperature outside the limit
1)
1
Status
On alarm
value
Red
Sensor error
•
Sensor breakage
•
Sensor short circuit
2
2
Status
Status
On alarm
value
On alarm
value
Red 2 Hz
Red 2 Hz
Measured value (PV) outside the sensor
limit
2)
2
Status
On alarm
value
Red 2 Hz
Summary of Contents for sitrans tr200
Page 2: ......
Page 20: ...Installation SITRANS TR200 TR300 20 Operating Instructions 04 2007 A5E01071992 01 ...
Page 32: ...Commissioning SITRANS TR200 TR300 32 Operating Instructions 04 2007 A5E01071992 01 ...
Page 66: ...Dimension drawings SITRANS TR200 TR300 66 Operating Instructions 04 2007 A5E01071992 01 ...
Page 74: ...Glossary SITRANS TR200 TR300 74 Operating Instructions 04 2007 A5E01071992 01 ...