SITRANS TR200/TR300
Operating Instructions, 04/2007, A5E01071992-01
19
Installation
4
The transmitter is secured to a 35 mm DIN rail to DIN EN 50022.
Comply with the ambient conditions specified in the technical data.
WARNING
Hazardous areas
•
Gas hazardous area:
–
The enclosure has IP20 degree of protection. In this way installation for 'intrinsically
safe' mode can be achieved without any additional enclosure, providing the supply
itself is intrinsically safe.
–
For nL and nA modes, use a suitable protective enclosure / terminal box which
satisfies at least IP54 degree of protection.
•
Dust hazardous zone:
For use in a dust hazardous zone, install in a suitable metal protective enclosure /
terminal box which satisfies at least IP6X degree of protection.
CAUTION
Electromagnetic Compatibility
If the sensor is installed outside closed buildings, the function of the device must be
checked following a lightning strike.