5.4 Connection in hazardous areas
SITRANS TR200/TR300
Operating Instructions, 04/2007, A5E01071992-01
27
Additional requirements for use in dust explosion protected areas
●
Only use the transmitter in a potentially explosive atmosphere with flammable dust when
the following points are ensured:
–
The transmitter is installed in a form B metal head in accordance with DIN 43729. The
metal head must have a protection of at least IP6X in accordance with EN 60529.
–
The transmitter is approved for use in an explosive atmosphere with flammable dust.
●
For a dust layer up to 5 mm thick a surface temperature of the housing 20 K above the
ambient temperature is permissible.
●
If the transmitter is used in a potentially explosive atmosphere consisting of an air/dust
mixture and the housing used is made of aluminum, observe the requirements from
chapter 6.2.1 of IEC 61241-0.