Technical data
11.1 Technical data
SITRANS TH200/TH300
74
Operating Instructions, 06/2010, A5E00393069-03
Millivolt transmitter input point
Measured variable
DC voltage
Sensor type
DC voltage source (DC voltage source is possible via a
resistor that is connected externally)
Units of measurement
mV
Measuring cycle
≤ 250 ms for 1 sensor with break monitoring
Break monitoring
Can be switched off
Measuring range
Setting range max. -100 ... 1100 mV
Min. measuring span
2 mV or 20 mV
Overload capacity of the input point
-1.5 ... 3.5 V DC
Input resistance
≥ 1 MΩ
Characteristic curve
Linear to voltage or special characteristic curve
Output
Output signal
4 ... 20 mA, two-wire line
With SITRANS TH300, additionally with communication
according to HART rev. 5.9
Auxiliary power supply
11 ... 35 V DC
(to 30 V with Ex ia and ib; to 32 V with Ex nA / nL / ic)
Max. load
(U
aux
-11 V)/0.023 A
Overrange
3.6 mA ... 23 mA continuously adjustable
(default range: 3.80 mA to 20.50 mA)
Error signal (e.g. in case of sensor failure) 3.6 mA ... 23 mA continuously adjustable
(default value: 22.8 mA)
Setting time:
Dead time
< 360 ms
T63 (without electrical attenuation,
without dead time)
< 260 ms
Attenuation
Software filter 1st order 0 ... 30 s (can be set in the
parameters)
Protection
Against reverse polarity
Galvanic isolation
Input to output 1.5 kV DC (1.0 kV AC)