SITRANS TH200/TH300
Operating Instructions, 06/2010, A5E00393069-03
23
Connecting
5
5.1
Safety notes on the connection
5.1.1
General safety notes on the connection
Note
To improve the resistance:
Lay signal cables separately from cables with voltages > 60 V.
Use cables with twisted wires.
Avoid getting too close to large electrical systems or use shielded cables.
Use shielded cables to ensure the full specification according to HART, revision 5.9 in
SITRANS TH300.
Use only cable entries and covers that are approved for the relevant use.
At an ambient temperature T ≥ 60°C, use heat-resistant cables approved for an ambient
temperature of at least 20 K higher.
Use cables with wires that have a maximum cross-sectional area of 2.5 mm
2
.