3.5 Communication
SITRANS TH200/TH300
18
Operating Instructions, 06/2010, A5E00393069-03
3.5.3
HART communication with supply via feed splitter
+$57bFRPPXQL
FDWRU
+$57
PRGHP
/RDGุ˖
56RU86%
)HHGVSOLWWHU
HJ1*$$
+$57MDFNV
7UDQVPLWWHU
6,75$167+
①
Only intrinsically safe HART communicators or HART modems are allowed to be used with an intrinsically safe supply.
②
HART communication via HART jacks of the feed splitter
③
Load ≥ 250 Ω only relevant if HART communication takes place via this branch. Otherwise, load of 0 to 650 Ω for
versions
①
or
②
Figure 3-4
HART communication with supply via feed splitter