
Commissioning
6.3 PROFIBUS configuration for SITRANS SL
SITRANS SL
Operating Instructions, 12/2010, A5E01132948-04
91
6.3.4
PG/PC interface setting
The SIMATIC MPI cable setting has to be made using the "Set PG/PC Interface" window
from the Options menu.
Prerequisite:
The connection between the PC and SITRANS SL has been established. The SIMATIC
Manager is installed on the PC and the Windows XP operating system has been started.
Procedure:
Start the operating program "Set PG/PC Interface" (start bar Start ➜ Programs ➜ SIMATIC
➜ Options ➜ Set PC-PG Interface).
1.
Select one of the following options in the list "Interface Parameter Assignment Used":
–
CP5512 (MPI) must be chosen for the connection to the MPI port of the PLC
–
CP5512 (PROFIBUS) must be chosen for the connection to the PROFIBUS connector
of the PLC
–
CP5613 2A
–
CP5611 PCMCIA
2.
The interface properties such as transmission rate can be selected from properties
window.