Installing
4.3 Electric connections non Ex
SITRANS SL
56
Operating Instructions, 12/2010, A5E01132948-04
Example: Analog out 0
!6,75$166/
9
&XVWRPHUVLGH
,
PHDV
5
ORDG
Figure 4-12 Using analog output
●
V
0
must be minimum 7.5 V and maximum 30 V DC.
●
R
load
can be maximum ((V
0
– 7.5 V)/0.025 A) Ω.
Note
SITRANS SL provides no supply voltage for the analog outputs, i.e. the analog outputs of
the SITRANS SL are passive and thus must be powered externally!