A5E33329501
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Page 177
mmm
mm
Pa
ra
m
e
te
rs
2.11.2.3. Relay Duration
The time in seconds from one change of state in the relay to the next.
2.11.2.4. Assigned Relay
Determines the relay assigned to time of day control.
2.11.2.5. Relay Logic
Use to change the behaviour of the relay assigned to time of day control.
Relay contact operation is NORMALLY CLOSED for alarms and NORMALLY
OPEN for controls.
By default a control contact is Normally Open. For
the corresponding relay coil is energized. By setting this parameter to
Normally Closed, the relay coil will be de-energized for the duration phase.
2.11.3. External Totalizer
Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model).
This function tracks the volume of material that passes through a system. The
external totalizer controls a relay to signal an external totalizing device. The
relay toggles on and off at a rate set by the parameters below. (For details on
relay behaviour under fail-safe conditions, see Miscellaneous relays on page
2.11.3.1. Enable
Enables/disables external totalizer relay control.
2.11.3.2. Multiplier
Use to scale the external totalizer up or down as required.
This allows the totalizer relay to click for different values of volume.
Example:
To click once every 4310 units, set
to 4310.
Values
Range: 1 to 9999
Default: 10
Options
*
RELAY 1
RELAY 2
RELAY 3
Options
*
NORMALLY OPEN
NORMALLY CLOSED
Note: Default settings in the parameter tables are indicated with an asterisk
(*) unless explicitly stated.
Options
ENABLED
*
DISABLED
Values
Range: 0.0000001 to 99999.000
Default: 1.000
Summary of Contents for SITRANS LUT400
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ...Controllori ad ultrasuoni Manuale d istruzioni 08 2012 SITRANS LUT400 HART SITRANS ...
Page 51: ...Pagina 32 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Collegamento Note ...
Page 81: ...Pagina 62 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML1998MV51 mmmmm Messa in esercizio Note ...
Page 151: ...Pagina 132 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Funzionamento AMS Note ...
Page 247: ...Pagina 228 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Manutenzione Note ...
Page 271: ...Pagina 252 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Dati tecnici Note ...
Page 287: ...Pagina 268 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm App A Rif tecnico Note ...
Page 303: ...Note Notes fm Page 2 Thursday October 11 2001 8 48 AM ...
Page 304: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 306: ...Operating Instructions SITRANS LUT400 HART 12 2014 Edition Ultrasonic Controllers ...
Page 319: ...Page 6 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Safety Notes Notes ...
Page 345: ...Page 32 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Connecting Notes ...
Page 375: ...Page 62 SITRANS LUT400 HART OPERATING INSTRUCTIONS 7ML1998MV01 mmmmm Commissioning Notes ...
Page 443: ...Page 130 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation Browser Notes ...
Page 445: ...Page 132 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation AMS Notes ...
Page 447: ...Page 134 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation FC375 Notes ...
Page 449: ...Page 136 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation FDT DTM Notes ...
Page 543: ...Page 230 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Maintenance Notes ...
Page 561: ...Page 248 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Troubleshooting Notes ...
Page 567: ...Page 254 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Technical Data Notes ...
Page 584: ...Page 271 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm App A Technical Ref ...
Page 585: ...Page 272 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm App A Technical Ref ...