Page 78
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
A5E33329501
mmmm
m
Gener
a
l Oper
at
ion
Temperature
Activates an alarm when the process temperature reaches a certain value (Low
Temperature Value ON for Low Temperature Alarm or High Temperature Value ON for a
High Temperature Alarm).
The temperature source can be the temperature sensor built into the transducer or an
external TS-3, as set by
. (Temperature Source is set in the Quick
Start Wizard, see page 39.)
Example: Setting a High Temperature Alarm
To assign Relay 3 to a high temperature alarm that activates when the temperature goes
above 30 °C do the following:
1.
Enable the High Temperature Alarm (set
= Enabled)
2.
Set
2.8.7.2. High Temperature Value ON
= 30
3.
Set
2.8.7.3. High Temperature Value OFF
= 28
4.
Set
to Relay 3.
The high temperature alarm will not de-activate until the temperature falls to 28 °C.
Use
to view the current state of the High Temperature Alarm.
Example: Setting a Low Temperature Alarm
To assign Relay 3 to a low level alarm that activates when the temperature falls below
-10 °C do the following:
1.
Enable the Low Level Alarm (set
= Enabled)
2.
Set
2.8.6.2. Low Temperature Value ON
= -10
3.
Set
2.8.6.3. Low Temperature Value OFF
= - 8
4.
Set
to Relay 3.
to view the current state of the Low Temperature Alarm.
Switch (Discrete Input) Alarm
Activates an alarm when a discrete input is in a pre-defined state.
Example: Setting a Switch Alarm
To assign Relay 3 to a switch alarm that is activated when DI 1 turns ON do the following:
1.
Enable the Switch (Discrete Input) Alarm (set
= Enabled)
2.
2.8.3.2. Discrete Input Number
= 1
3.
Set
to ON.
4.
Set
to Relay 3.
to view the current state of the Switch Alarm.
Summary of Contents for SITRANS LUT400
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ...Controllori ad ultrasuoni Manuale d istruzioni 08 2012 SITRANS LUT400 HART SITRANS ...
Page 51: ...Pagina 32 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Collegamento Note ...
Page 81: ...Pagina 62 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML1998MV51 mmmmm Messa in esercizio Note ...
Page 151: ...Pagina 132 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Funzionamento AMS Note ...
Page 247: ...Pagina 228 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Manutenzione Note ...
Page 271: ...Pagina 252 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Dati tecnici Note ...
Page 287: ...Pagina 268 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm App A Rif tecnico Note ...
Page 303: ...Note Notes fm Page 2 Thursday October 11 2001 8 48 AM ...
Page 304: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 306: ...Operating Instructions SITRANS LUT400 HART 12 2014 Edition Ultrasonic Controllers ...
Page 319: ...Page 6 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Safety Notes Notes ...
Page 345: ...Page 32 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Connecting Notes ...
Page 375: ...Page 62 SITRANS LUT400 HART OPERATING INSTRUCTIONS 7ML1998MV01 mmmmm Commissioning Notes ...
Page 443: ...Page 130 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation Browser Notes ...
Page 445: ...Page 132 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation AMS Notes ...
Page 447: ...Page 134 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation FC375 Notes ...
Page 449: ...Page 136 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation FDT DTM Notes ...
Page 543: ...Page 230 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Maintenance Notes ...
Page 561: ...Page 248 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Troubleshooting Notes ...
Page 567: ...Page 254 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Technical Data Notes ...
Page 584: ...Page 271 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm App A Technical Ref ...
Page 585: ...Page 272 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm App A Technical Ref ...