2.5.7. Manual Value
The mA value to use when Current Output Function (2.5.1.) is set to Manual.
Allows you to use a simulated value to test the functioning of the loop. You can
enter 4 mA, 20 mA, or any other user-defined value within the range.
a) First set Current Output Function (2.5.1.) to Manual.
b) Set this parameter to the desired mA value.
c) After completing the test, remember to reset Current Output Function
(2.5.1.) to the previous setting.
Via AMS Device Manager or FC375/475:
Open the menu Configure/Setup > Operation > Select Analog Output.
Via SIMATIC PDM:
Open the menu Device – Loop Test.
2.5.8. Current Output Value
Read only. Displays the current mA value, including a simulated value entered
to test the functioning of the loop.
2.6. Volume
Carries out a volume conversion from a level value.
2.6.1. Vessel Shape
89Defines the vessel shape and allows the LUT400 to calculate volume
instead of level. If None is selected, no volume conversion is performed.
Select the vessel shape matching the monitored vessel or reservoir.
Values
Range: 3.5 to 22.8 mA
Default: 3.58
Values
Range: 3.5 to 22.8 mA
Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
Vessel Shape
LCD DISPLAY/
Description
Also
required
*
None
NONE/
No volume calculation
required
N/A
LINEAR/
Upright, linear (flat bottom)
maximum
volume
CYLINDER/
Flat end horizontal cylinder
maximum
volume
Summary of Contents for SITRANS LUT400
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ...Controllori ad ultrasuoni Manuale d istruzioni 08 2012 SITRANS LUT400 HART SITRANS ...
Page 51: ...Pagina 32 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Collegamento Note ...
Page 81: ...Pagina 62 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML1998MV51 mmmmm Messa in esercizio Note ...
Page 151: ...Pagina 132 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Funzionamento AMS Note ...
Page 247: ...Pagina 228 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Manutenzione Note ...
Page 271: ...Pagina 252 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm Dati tecnici Note ...
Page 287: ...Pagina 268 SITRANS LUT400 HART MANUALE D ISTRUZIONI 7ML19985MV51 mmmmm App A Rif tecnico Note ...
Page 303: ...Note Notes fm Page 2 Thursday October 11 2001 8 48 AM ...
Page 304: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 306: ...Operating Instructions SITRANS LUT400 HART 12 2014 Edition Ultrasonic Controllers ...
Page 319: ...Page 6 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Safety Notes Notes ...
Page 345: ...Page 32 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Connecting Notes ...
Page 375: ...Page 62 SITRANS LUT400 HART OPERATING INSTRUCTIONS 7ML1998MV01 mmmmm Commissioning Notes ...
Page 443: ...Page 130 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation Browser Notes ...
Page 445: ...Page 132 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation AMS Notes ...
Page 447: ...Page 134 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation FC375 Notes ...
Page 449: ...Page 136 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Operation FDT DTM Notes ...
Page 543: ...Page 230 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Maintenance Notes ...
Page 561: ...Page 248 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Troubleshooting Notes ...
Page 567: ...Page 254 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm Technical Data Notes ...
Page 584: ...Page 271 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm App A Technical Ref ...
Page 585: ...Page 272 SITRANS LUT400 HART OPERATING INSTRUCTIONS A5E33329501 mmmmm App A Technical Ref ...