Modbus
Address
Parameter
Default
value
Value range
Ac‐
cess
level
Description
43001
106 Flow rate
Read
Actual flow value
43136
107 Relative flow rate
0
Read
Actual flow value in relation to Qmax
43035
108 Actual velocity for path 1
0
Read
The actual flow velocity for path 1 in
m/s (SI-unit)
43046
109 Actual velocity for path 2
0
The actual flow velocity for path 2 in
m/s (SI-unit).
Valid for 2-path solutions only
43026
110 Path 1 gain step
15
1 to 15
Read
Amplifier setting when measuring
path 1
43037
111 Path 2 gain step
15
1 to 15
Read
Amplifier setting when measuring
path 2.
Valid for 2-path solutions only
Pulse A B
40817
430 Output A enable
Product
depend‐
ent
No, Yes
R/W
Select "Yes" to enable output A
40818
431 Pulse A direction
Forward
Forward, Re‐
verse, For‐
ward net, Re‐
verse net
R/W
Pulse output calculation on pure for‐
ward flow or pure reverse flow - or net
flow for forward and reverse pulse
flow.
Valid if pulse output A is enabled
40819
432 Amount per pulse A
Product
depend‐
ent
0.000001 to
1000000000
R/W
Volume per pulse and selected unit
Valid if pulse output A is enabled.
40821
433 Pulse width for pulse A
Product
depend‐
ent
5, 10, 20, 50,
100, 200, 500
ms
R/W
Pulse length when the pulse is ac‐
tive.
Valid if pulse output A is enabled
40822
440 Output B enable
Product
depend‐
ent
No, Yes
R/W
Select "Yes" to enable output B
40823
441 Pulse B function
Product
depend‐
ent
Pulse, Alarm,
Call up
R/W
Configuration of output B as pulse -
alarm or call up function.
Valid if pulse output B is enabled
40824
442 Pulse B direction
Reverse
Forward, Re‐
verse, For‐
ward net, Re‐
verse net.
R/W
Pulse output calculation on pure for‐
ward flow or pure reverse flow - or net
flow for forward and reverse pulse
flow.
Valid if pulse output B is enabled and
pulse function selected
40825
443 Amount per pulse B
Product
depend‐
ent
0.000001 to
1000000000
R/W
Volume per pulse.
Valid if pulse output B is enabled and
pulse function selected
40827
444 Pulse width for pulse B
Product
depend‐
ent
5, 10, 20, 50,
100, 200, 500
ms
R/W
Pulse length when the pulse is ac‐
tive.
Valid if pulse output B is enabled and
pulse function selected
Parameter lists
A.2 Output
FUS380/FUE380
Operating Instructions, 09/2016, A5E00730100-AB