Modbus RTU RS-485
4
SFIDK.PS.023.D2.02
2.
Technical data
Siemens Flow Instruments Modbus RTU specification
Device type
Slave
Baud rates
1200, 2400, 4800, 9600, 19200, 38400, 57600,
76800, 115200 bits/sec.
Number of stations
Recommended: max. 31 per segment without repeaters
Device address range
1-247
Protocol
RTU
(Other Modbus protocols like ASCII, Plus or TCP/IP are
not
supported)
Electrical interface
RS-485, 2 wire
Connecter type
Screw terminals
Supported function codes
1 read coils
3 read holding registers
5 write single coil
16 write multiple registers
17 report slave ID
Broadcast
No
*)
Maximum cable length
1200 meters (@115200 bits/sec.)
Standard
Modbus over serial line v1.0*)
Certified
No
Device profile
None
*)
Standard restriction
The standard requires a LED indicator for visual diagnosis. This module do not support a LED indicator.
Instead comprehensive display information is available. This device does not react to any Broadcast
commands.