![Siemens SITRANS F C MASSFLO series Operating Manual Download Page 14](http://html.mh-extra.com/html/siemens/sitrans-f-c-massflo-series/sitrans-f-c-massflo-series_operating-manual_1265486014.webp)
Modbus RTU RS-485
14
SFIDK.PS.023.D2.02
Modbus
Modbus
No. of
Data
Read/
register
address
bytes
type
Description
write
4:03003
3002
4
Float
Absolute Volumeflow (m
3
/s)
R
4:03015
3014
8
Double
Totalizer 1 (m
3
)
R
4:03019
3018
8
Double
Totalizer 2/Batch (m
3
)
R
4:03023
3022
4
Float
Totalizer 1 (m
3
)
R
4:03025
3024
4
Float
Totalizer 2/Batch (m
3
)
R
6.
Modbus holding registers
Modbus
Modbus
No. of
Data
Read/
register
address
bytes
type
Description
write
4:03001
3000
4
Float
Absolute Massflow (kg/s)
R
4:03003
3002
4
Float
Absolute Volumeflow (m
3
/s)
R
4:03005
3004
4
Float
Absolute Density (kg/m
3
)
R
4:03007
3006
4
Float
Sensor temperature (
°
C)
R
4:03009
3008
4
Float
Fraction A (kg/s)
R
4:03011
3010
4
Float
Fraction B (kg/s)
R
4:03013
3012
4
Float
% fraction A (%)
R
4:03015
3014
8
Double
Totalizer 1 (kg or m
3
)
R
4:03019
3018
8
Double
Totalizer 2/Batch (kg or m
3
)
R
4:03023
3022
4
Float
Totalizer 1 (kg or m
3
)
R
4:03025
3024
4
Float
Totalizer 2/Batch (kg or m
3
)
R
4:03100
3099
2
Byte
Update rate set:
0 = Reserved
1 = All process data updated
with 2 Hz
R/W
2 = Like set 1, but with
Massflow 10 Hz
3 = Like set 2, but with
Totalizers 5 Hz
MASS
Modbus
Modbus
No. of
Data
Read/
register
address
bytes
type
Description
write
4:00501
500
2
Word
No. of ParityErrors
R
4:00502
501
2
Word
No. of FramingErrors
R
4:00504
503
2
Word
No. of CRC Errors
R
4:00505
504
2
Word
No. of Ok Messages (received)
R
4:00508
507
4
Dword
InterFrameSpace (us)
R
4:00512
511
2
Word
Response Timeout (ms)
R/W
4:00513
512
2
Word
Response Delay (ms)
R/W
4:00514
513
2
Byte
10xInterFrameSpace (10 x chars)
R/W
4:00515
514
4
Dword
Baudrate as double word
R
4:00528
528
2
Byte
Device address (1 - 247)
R/W
4:00529
529
2
Byte
Baudrate:
0 = 1200
1 = 2400
2 = 4800
3 = 9600
R/W
4 = 19200
5 = 38400
6 = 57600
7 = 76800
8 = 115200
4:00530
530
2
Byte
Parity/framing:
0 = 8, E, 1
1 = 8, O, 1
R/W
2 = 8, N, 2
3 = 8, N, 1
6.1 Process data