![Siemens SITRANS F C MASSFLO series Operating Manual Download Page 26](http://html.mh-extra.com/html/siemens/sitrans-f-c-massflo-series/sitrans-f-c-massflo-series_operating-manual_1265486026.webp)
Modbus RTU RS-485
26
SFIDK.PS.023.D2.02
In the following the coils for the USM II Modbus RTU module are described.
7.
Modbus coils
7.
Modbus coils
Figure:
Memory map for coils
Modbus
Modbus
Data
Read/
register
address
type
Description
write
0:00001
0
Coil
Restart Modbus communication:
Write:
0 = No effect
1 = Restart
R/W
Read:
always 0
Modbus
Modbus
Data
Read/
register
address
type
Description
write
0:00009
8
Coil
Start auto zero adjust:
Write:
0 = No effect
1 = StartRead:
R/W
0 = Idle1 = Busy
Modbus
Modbus
Data
Read/
register
address
type
Description
write
0:00010
9
Coil
Reset totalizer 1:
Write:
0 = No effect
1 = ResetRead:
R/W
always 0
0:00011
10
Coil
Hold totalizer 1:
Write:
0 = Run
1 = HoldRead:
R/W
0 = Not held1 = Held
0:00012
11
Coil
Reset totalizer 2:
Write:
0 = No effect
1 = ResetRead:
R/W
always 0
0:00013
12
Coil
Hold totalizer 2:
Write:
0 = Run
1 = HoldRead:
R/W
0 = Not held1 = Held
Modbus
Modbus
Data
Read/
register
address
type
Description
write
0:00014
13
Coil
Start Batch:
Write:
0 = Stop Batch
1 = Start BatchRead:
R/W
0 = Stopped1 = Not stopped
0:00015
14
Coil
Pause Batch:
Write:
0 = Resume Batch
1 = Pause BatchRead:
R/W
0 = Not paused1 = Paused
7.1 Communication
settings
7.2 Auto zero adjust
7.3 Totalizer
7.4 Batch
Control/status
0
20
655535