Modbus RTU RS-485
20
SFIDK.PS.023.D2.02
Modbus
Modbus
No. of
Data
Read/
register
address
bytes
type
Description
write
4:02214
2213
4
Float
Frequency 1 Timeconstants
R/W
4:02216
2215
2
Byte
Limit Digital selection:
0 = Off (read only)
1 = Massflow
2 = Fraction A
3 = Fraction B
R/W
4 = Volumeflow
5 = Sensor temp.
6 = Density
7 = % fraction A
4:02217
2216
2
Byte
Limit Digital mode:
0 = 1 setpoint
R/W
1 = 2 setpoints
4:02218
2217
4
Float
Limit Digital Setpoint min. (1/100%)
R/W
4:02220
2219
4
Float
Limit Digital Setpoint max. (1/100%)
R/W
4:02222
2221
4
Float
Limit Digital Hysteresis (1/100%)
R/W
4:02224
2223
2
Byte
Relay Output 1 function:
0 = Off
3 = Error Level
R/W
4 = Error Number
5 = Direction/Limit
4:02225
2224
2
Byte
Limit Relay selection:
0 = Off
1 = Massflow
2 = Fraction A
3 = Fraction B
R/W
4 = Volumeflow
5 = Sensor temp.
6 = Density
7 = % fraction A
4:02226
2225
2
Byte
Limit Relay mode:
0 = 1 setpoint
R/W
1 = 2 setpoints
4:02227
2226
4
Float
Limit Relay Setpoint min. (1/100%)
R/W
4:02229
2228
4
Float
Limit Relay Setpoint max. (1/100%)
R/W
4:02231
2230
4
Float
Limit Relay Hysteresis (1/100%)
R/W
4:02233
2232
2
Byte
Error number (0-255)
R/W
4:02234
2233
2
Byte
Batch selection:
0 = Off (read only)
1 = Massflow
2 = Fraction A
R/W
3 = Fraction B
4 = Volumeflow
4:02235
2234
4
Float
Batch Quantity (kg or m
3
)
R/W
4:02237
2236
4
Float
Batch Compensation
R/W
4:02239
2238
4
Float
Batch Lead constant
R/W
4:02241
2240
2
Byte
Batch Time error on/off:
0 = Off
R/W
1 = On
4:02242
2241
4
Float
Max. Batch time (s)
R/W
4:02244
2243
2
Byte
Batch overrun on/off:
0 = Off
R/W
1 = On
4:02245
2244
4
Float
Batch overrun error (kg or m
3
)
R/W
4:02247
2246
2
Byte
Batch counter up/down
0 = Down
R/W
1 = Up
4:02250
2249
4
Dword
Batch cycle counter
R
4:02291
2290
4
Float
Mass or Volume
per pulse (kg or m
3
)
R/W
4:02296
2295
2
Byte
Quadratur:
0 = Off
R/W
1 = On
6.
Modbus holding registers
6.6 Output
(continued)
MASS 6000