Parameter assignment
5.12 Parameterizing the High Feature 3RW5 HMI
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
113
5.12
Parameterizing the High Feature 3RW5 HMI
Requirements
●
3RW5 HMI High Feature
Setting options
●
3RW5 HMI High Feature
Menu: "Parameters > HMI"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
●
With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
●
With a fieldbus via a 3RW5 communication module:
–
With SIRIUS Soft Starter ES (TIA Portal) Premium (only via a 3RW5 PROFINET or
PROFIBUS communication module)
–
Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
–
User program
You can find further information on the parameters that can be set via the fieldbus in the
Equipment Manual of the respective 3RW5 communication module.
Parameter
Parameter
Description
Local interface activated
(via 3RW5 HMI High Feature only)
The parameter is only visible if the local interface is enabled (factory setting).
Disables the local interface of the 3RW5 HMI High Feature.
Before you can connect a PC with SIRIUS Soft Starter ES (TIA Portal) to the
3RW50 soft starter via the local interface, the local interface must be enabled. You
can prevent unauthorized access via SIRIUS Soft Starter ES (TIA Portal) by disabling
the local interface.
Local interface deactivated
(via 3RW5 HMI High Feature only)
The parameter is only visible if the local interface is disabled.
Enables the local interface of the 3RW5 HMI High Feature.
Timer lighting dark
If no keys on the 3RW5 HMI High Feature are pressed, the display will shut down
after a specified time period has elapsed. The parameter value "0" deactivates the
shutdown of the display.
•
Factory setting: 5 min
•
Setting range: 0 ... 60 min
•
Increment: 1 min