Connecting
4.5 Mounting terminal covers on main circuit connections
SIRIUS 3RW50 soft starter
78
Manual, 09/2019, A5E35628455002A/RS-AA/001
4.5
Mounting terminal covers on main circuit connections
Requirements
●
Terminal cover (accessory) for 3RW50 soft starter
Note
Touch protection by terminal cover.
Touch protection according to EN 50274 finger-safe only for vertical contact from the front.
Procedure
DANGER
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before working on this device.
●
Make sure that you mount the terminal cover the right way round on the connecting
terminal, as shown in the diagram.