Connecting
4.11 COM connection cable
SIRIUS 3RW50 soft starter
88
Manual, 09/2019, A5E35628455002A/RS-AA/001
4.11.3
Removing the COM connecting cable on the 3RW5 communication module
Requirements
●
3RW5 communication module (accessory)
●
Removed bus connector (fieldbus)
You can find further information on connecting to the fieldbus in the Equipment Manual
for the respective 3RW5 communication module.
●
Cover cap
NOTICE
Damage to property due to electrical voltage
Switch off the power to the 3RW5 soft starter before starting work (main and control supply
voltage).
Procedure
Illustration similar
1.
Loosen die securing mechanism on the bus connector of the COM connecting cable.
2.
Pull the bus connector of the COM connecting cable out of the plug-in connection of the
3RW5 communication module for the 3RW5 soft starter.
Result
You have disconnected the 3RW5 communication module from the 3RW50 soft starter.
Place the cover cap onto the front plug-in connection of the 3RW5 communication module
for the 3RW5 soft starter.