Parameter assignment
5.8 Setting parameterizing mode via key combination on the 3RW50 soft starter
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
103
Setting of the parameter "Output ON / RUN" (selection in Step 1):
Output ON / RUN
"RN" LED
"ER" LED
"MT" LED
Set parameter value
Off
Off
Off
Output function ON
Off
Off
Lights up
yellow
Output function RUN
3.
Switch off the supply voltage of the 3RW50 soft starter for at least 5 s.
The set parameters and parameter values are stored.
4.
Switch the supply voltage of the 3RW50 soft starter on again.
The set parameters and parameter values are now active.
Result
You have set the parameters in the parameterizing mode.
Further information
For more information about the parameters, see Chapters Parameterizing output 13 / 14
(output signal ON or RUN) (Page 99) and Control via digital input (Page 139).