Mounting and dismantling
3.4 Connecting the 3RW5 HMI
SIRIUS 3RW50 soft starter
58
Manual, 09/2019, A5E35628455002A/RS-AA/001
Procedure for connecting with the HMI connecting cable
●
Observe the coding of the plug and socket
①
.
●
Lock the connector in the socket
②
.
●
The HMI connecting cable in the cable duct of the 3RW5 HMI Standard may only be
routed downward.
Make sure that you install the cable in accordance with EMC requirements. For example,
route data cables separately from the motor cable. Connect both sides of shielded cables
over a large surface area.
3.4.3
Installing the High Feature 3RW5 HMI in the control cabinet door
Requirements
●
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
●
3RW5 HMI High Feature (accessories)
●
HMI connecting cable (accessory) of suitable length connected to the soft starter
(Page 55)
●
Cutout of suitable size in the control cabinet door
●
Device depth of the High Feature 3RW5 HMI:
–
Total depth: 32 mm
–
Embedded depth: 26 mm
●
Permissible wall thickness of the cabinet door:
–
Without IP65 door mounting kit: 1.5 to 3.0 mm
–
With IP65 door mounting kit: 1.0 to 7.0 mm
For using door mounting kit IP65:
●
IP65 door mounting kit (accessory)
The fixing brackets with marking "002" are intended for a 3RW5 HMI High Feature.
●
Screwdriver PZ2