Jumper Settings
−
Bay Unit
363
7SS52 V4 Manual
C53000-G1176-C182-3
1) Delivery setting
Table A-20
Jumper settings for different control voltages of the binary inputs of the EFE_10
module
Setting for nominal control voltage
Name
24 V
60 V
110 V
220 V
1)
BI 1
X37
X36
X35
-
BI 2
X40
X39
X38
-
BI 3
X43
X42
X41
-
BI 4
X46
X45
X44
-
BI 5
X49
X48
X47
-
BI 6
X52
X51
X50
-
BI 7
X55
X54
X53
-
BI 8
X58
X57
X56
-
BI 9
X79
X78
X77
-
BI 10
X76
X75
X74
-
www
. ElectricalPartManuals