Connecting
6.6 Connecting I/O modules
SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
59
X1: Current measurement
8-pin connector with spring-loaded connection and interlock. The mating connectors are
included in the scope of supply.
Pin
Assignment
Pin
1
I1 -
I1 +
2
3
I2 -
I2 +
4
5
I3 -
I3 +
6
7
Reserved
Reserved
8
Note
The connection cable for the current measurement must not be longer than 30 m.
X2: Voltage measurement
6-pin connector with spring-loaded connection and interlock. The mating connectors are
included in the scope of supply.
Pin
Assignment
1
Reserved
2
Phase 1
3
Phase 2
4
Phase 3
5
PEN conductor
6
Reserved