Communications
10.2 Acyclic data exchange
SIPLUS HCS4200
100
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
Data set 200 "measured values"
Byte
Description
Data POM 1
0
Internal temperature
1
Reserved
2,3
Frequency (with one decimal place)
Data POM 2
…
…
…
…
…
Data for POM 12/24
…
…
PROFINET: Definition is via an array [1..24] with one element of type "Structure".
PROFIBUS: Definition is via an array [1..12] with one element of type "Structure".
This comprises two elements of type "Byte" and one element of type "Word".
The POM number corresponds to the array index.
The length of the data set corresponds to the number of POMs that are used.
Data set 201 "versions"
Byte
Description
CIM / PM
0…3
FW version of CIM fieldbus controller
4…7
FW version of CIM HCS master
8
HW version of CIM
9
HW version of PM
10…13
FW version of PM
POM 1
14…17
Firmware version POM 1
18
Hardware version triac POM 1
19
Reserved
POM 2
…
…
…
…
…
POM 12/24
…
…
All firmware versions contain one element of type "Char" and three elements of type "Byte".
The hardware versions are all of type "Byte".
PROFINET: Definition of the POM versions is via an array [1…24] with one element of type
"Structure".
PROFIBUS: Definition of the POM versions is via an array [1…12] with one element of type
"Structure".
The POM number corresponds to the array index.
The length of the data set corresponds to the number of POMs that are used. The entry for
CIM with I/O module is always available, even if the I/O module is not plugged in.