SIPLUS HCS4200
Operating Instructions, 11/2015, A5E35066204A/RS-AA/002
127
Technical specifications
13
13.1
Technical specifications for Rack4200
product brand name
SIPLUS
Product designation
Rack4200 for 12 POM
Rack4200 for 4 POM
General technical data:
Equipment marking / acc. to DIN EN 81346-2
K
Number of slots
12
4
Type of power output / connectable
POM4220
Supply voltage:
Power capacity
•
without fan / per rack / maximum
88 kW
29 kW
•
with fan / per rack / maximum
193 kW
64 kW
Communication:
Design of the interface
system interface
Mechanical data:
Mounting position
horizontal
Mounting type
Control cabinet backplane
Type of ventilation
Self ventilation or forced ventilation
Vibration resistance
•
during operation / acc. to IEC 60068-2-6
10 ... 58 Hz / 0.
075
mm, 58 ...
150 Hz / 1g
10 ... 58 Hz / 0.075 mm, 58 ...
150 Hz / 1 g
•
during storage / acc. to IEC 60068-2-6
5 ...
8.5
Hz / 3.5 mm,
8.5
...
500 Hz / 1g
5 ... 8.5 Hz / 3,5 mm, 8.5 ... 500
Hz / 1 g
Shock resistance
•
acc. to IEC 60068-2-27
15g / 11 ms / 3 shocks / axis
•
acc. to IEC 60068-2-29
25 g / 6 ms / 1000 shocks / axis
Protection class IP
IP20
Depth
293 mm
Height
285 mm
Width
488 mm
204 mm
Electromagnetic compatibility:
EMC emitted interference
Limit value in accordance with IEC 61000-6-4:2007 + A1:2011
Field-bound parasitic coupling / acc. to IEC
61000-4-3
10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7
GHz)
Electrostatic discharge / acc. to IEC 61000-4-2
4 kV contact discharge / 8 kV air discharge