05.91
7 ELG-Specific Signals (DB 29)
7.3 Signals to ELG (DB 29)
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
2ND FLANK APPROACHED
DW m + 3, bit 10
0/1 transition:
The effect of a signal change depends on the 2ND FLANK STORED signal.
a) 2ND FLANK STORED = 0:
The actual position of the axis is stored and overrunning of the workpiece
flank is prevented with the 0/1 transition of 2ND FLANK APPROACHED
(see 1ST FLANK APPROACHED). The NC sets the 2ND FLANK STORED
signal and automatically approaches the centre position between the two
flanks (see CENTRE POSITION REACHED).
b) 2ND FLANK STORED = 1:
The stored position of the 2nd workpiece flank is deleted and the associated
traversing limit for the axis is cancelled. The 2ND FLANK STORED signal is
cancelled. This allows the information on the 2nd workpiece flank to be
corrected.
1/0 transition:
The PLC user program must reset the 2ND FLANK APPROACHED signal if
the status of the 2ND FLANK STORED signal has changed.
Notes:
•
The signal is effective only with SAC ACTIVE = 1.
•
The 1st flank must be specified before defining the 2nd flank position with 2ND FLANK
APPROACHED.
FA 1: m=0
FA 2: m=4
FA 3: m=8
©
Siemens AG 1991 All Rights Reserved 6ZB5 410-0HE02
7
–
23
SINUMERIK 880 (PJ)