Technical data
7.6 Technical data, 400 V inverters
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
85
Table 7- 21 PM240-2, IP20, Frame Size D, 3-ph. AC 380 V … 480 V
Article no. without filter
Article no. with filter
6SL3210-1PE27-5UL0
6SL3210-1PE27-5AL0
LO base load output
37 kW
LO base load input current
70 A
LO base load output current
75 A
HO base load output
30 kW
HO base load input current
62 A
HO base load output current
60 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3830 (100 A)
100 A
Power loss without filter
1.09 kW
Power loss with filter
1.10 kW
Required cooling air flow
55 l/s
Weight without filter
17 kg
Weight with filter
18.5 kg
Table 7- 22 PM240-2, IP20, Frame Size E, 3-ph. AC 380 V … 480 V
Article no. without filter
Article no. with filter
6SL3210-1PE28-8UL0
6SL3210-1PE28-8AL0
6SL3210-1PE31-1UL0
6SL3210-1PE31-1AL0
LO base load output
45 kW
55 kW
LO base load input current
86 A
104 A
LO base load output current
90 A
110 A
HO base load output
37 kW
45 kW
HO base load input current
78 A
94 A
HO base load output current
75 A
90 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3832 (125 A)
125 A
3NA3836 (160 A)
150 A
Power loss without filter
1.29 kW
1.65 kW
Power loss with filter
1.30 kW
1.67 kW
Required cooling air flow
83 l/s
83 l/s
Weight without filter
26 kg
26 kg
Weight with filter
28 kg
28 kg
Summary of Contents for SINAMICS PM240-2
Page 1: ......
Page 2: ......
Page 8: ...Table of contents Power Module PM240 2 8 Hardware Installation Manual 01 2017 A5E33294624B AE ...
Page 104: ...Spare parts Power Module PM240 2 104 Hardware Installation Manual 01 2017 A5E33294624B AE ...
Page 143: ......