Technical data
7.6 Technical data, 400 V inverters
Power Module PM240-2
86
Hardware Installation Manual, 01/2017, A5E33294624B AE
Table 7- 23 PM240-2, IP20, Frame Size F, 3-ph. AC 380 V … 480 V
Article no. without filter
Article no. with filter
6SL3210-1PE31-5UL0
6SL3210-1PE31-5AL0
6SL3210-1PE31-8UL0
6SL3210-1PE31-8AL0
6SL3210-1PE32-1UL0
6SL3210-1PE32-1AL0
LO base load output
75 kW
90 kW
110 kW
LO base load input current
140 A
172 A
198 A
LO base load output current
145 A
178 A
205 A
HO base load output
55 kW
75 kW
90 kW
HO base load input current
117 A
154 A
189 A
HO base load output current
110 A
145 A
178 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3140 (200 A)
200 A
3NA3142 (224 A)
250 A
3NA3250 (300 A)
300 A
Power loss without filter
1.91 kW
2.46 kW
2.28 kW
Power loss with filter
1.93 kW
2.48 kW
2.30 kW
Required cooling air flow
153 l/s
153 l/s
153 l/s
Weight without filter
57 kg
57 kg
61 kg
Weight with filter
63 kg
63 kg
65 kg
Table 7- 24 PM240-2, IP20, Frame Size F, 3-ph. AC 380 V … 480 V
Article no. without filter
Article no. with filter
6SL3210-1PE32-5UL0
6SL3210-1PE32-5AL0
LO base load output
132 kW
LO base load input current
242 A
LO base load output current
250 A
HO base load output
110 kW
HO base load input current
218 A
HO base load output current
205 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3252 (315 A)
350 A
Power loss without filter
2.98 kW
Power loss with filter
3.02 kW
Required cooling air flow
153 l/s
Weight without filter
61 kg
Weight with filter
65 kg