Connecting-up
5.2 Connecting the line and motor cable at the inverter
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
53
Table 5- 3
Permissible cable lengths for the motor connection, FSF
Inverter
with internal
C2 filter
with or without filter, with or
without output reactor
without filter, with two output
reactors in series
EMC category Second Envi-
ronment, C2
No EMC category
Cable
Shielded
Shielded
Unshielded
Shielded
Unshielded
200 V
---
300 m
450 m
525 m
800 m
400 V
150 m
300 m
450 m
525 m
800 m
690 V
150 m
1)
300 m
450 m
525 m
800 m
1)
only C3
5.2.3
Connection terminals at the inverter
Table 5- 4
Connection, cross-section and tightening torque for PM240-2 Power Modules
Inverters
Connection
Cross-section, tightening torque
Stripped
insulation
length
Metric
Imperial
FSA
Line supply, motor,
DC link and braking
resistor
Plug connector
with screw termi-
nals
1.5 … 2.5 mm
2
, 0.5 Nm
16 … 14 AWG, 4.5 lbf in 8 mm
FSB
1.5 … 6 mm
2
, 0.6 Nm
16 … 10 AWG, 5.5 lbf in 8 mm
FSC
6 …16 mm², 1.3 Nm
10 … 6 AWG, 12 lbf in
10 mm
FSD
Line supply, motor
and DC link
Screw-type termi-
nal
10 … 35 mm
2
,
2.5 … 4.5 Nm
20 … 10 AWG, 22 lbf in
8 … 2 AWG, 40 lbf in
18 mm
Braking resistor
2.5 … 16 mm
2
,
1.2 … 1.5 Nm
20 … 6 AWG, 15 lbf in
10 mm
FSE
Line supply, motor
and DC link
Screw-type termi-
nal
25 … 70 mm
2
, 8 … 10 Nm 6 … 3/0 AWG,
88.5 lbf in
25 mm
Braking resistor
10 … 35 mm
2
,
2.5 … 4.5 Nm
20 … 10 AWG, 22 lbf in
8 … 2 AWG, 40 lbf in
18 mm
FSF
Line supply, motor
and DC link
Cable lug accord-
ing to SN71322
35 … 2 × 120 mm
2
,
22 … 25 Nm
1 … 2 × 4/0 AWG,
210 lbf.in
--
Braking resistor
Screw-type termi-
nal
25 … 70 mm
2
, 8 … 10 Nm 6 … 3/0 AWG,
88.5 lbf in
25 mm
Summary of Contents for SINAMICS PM240-2