Technical data
7.5 Technical data, 200 V inverters
Power Module PM240-2
Hardware Installation Manual, 01/2017, A5E33294624B AE
77
Table 7- 10 PM240-2, IP20, frame size D, 3 AC 200 V … 240 V
Article number without filter
6SL3210-1PC24-2UL0 6SL3210-1PC25-4UL0
6SL3210-1PC26-8UL0
LO base load power
11 kW
15 kW
18.5 kW
LO base load input current
40 A
51 A
64 A
LO base load output current
42 A
54 A
68 A
HO base load power
7.5 kW
11 kW
15 kW
HO base load input current
36 A
43 A
56 A
HO base load output current
35 A
42 A
54 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3822 (63 A)
60 A
3NA3824 (80 A)
70 A
3NA3830 (100 A)
90 A
Power loss
0.45 kW
0.61 kW
0.82 kW
Required cooling air flow
55 l/s
55 l/s
55 l/s
Weight
17 kg
17 kg
17 kg
Table 7- 11 PM240-2, IP20, frame size E, 3 AC 200 V … 240 V
Article number without filter
6SL3210-1PC28-0UL0 6SL3210-1PC31-1UL0
LO base load power
22 kW
30 kW
LO base load input current
76 A
98 A
LO base load output current
80 A
104 A
HO base load power
18.5 kW
22 kW
HO base load input current
71 A
83 A
HO base load output current
68 A
80 A
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NA3830 (100 A)
100 A
3NA3836 (160 A)
150 A
Power loss
0.92 kW
1.28 kW
Required cooling air flow
83 l/s
83 l/s
Weight
26 kg
26 kg