04/2005 Commissioning
SINAMICS G110 Operating Instructions
6SL3298-0AA11-0BP0
43
For a complete description of the buttons on the BOP and the procedure for
attaching the BOP to the inverter, see Appendices C and D starting on page 82.
For more information on using the BOP, please refer to Section 3.3.2 on page 37.
If a BOP is fitted and the output frequency is selected to be displayed (P0005 = 21)
the corresponding setpoint is displayed approximately every 1.0 seconds while the
inverter is stopped.
Set P0719 = 11 or set the command source P0700 = 1 and the frequency setpoint
P1000 = 1 for complete inverter control when in BOP mode (see also P1031 and
P1040).
STARTER Software
Warning
During the parameter download with the STARTER commissioning tool to the
inverter, the digital output may produce a spurious signal.
Prior to performing a download to the inverter appropriate counter-measures
must
be taken to ensure that any suspended load is secured, for example, by the use of
external brakes or the load being lowered to ground level and secured.
To assist in the quick and efficient changing of parameters and commissioning, the
software tool STARTER can be used. This software is provided on the
Documentation and PC Tool CD-ROM (orderable as a separate item) or it can be
downloaded from the internet.
STARTER provides the user with a graphical interface that provides easy access to
the inverter’s parameters via a parameter database or a configuration wizard to
guide the user through the correct set-up and configuration procedures.
The STARTER software runs on the following operating systems:
¾
Windows NT
¾
Windows 2000
¾
Windows XP Professional
The STARTER software is self-explanatory and is supported by means of an
on-line help facility.
In order to use the STARTER software, the user will require the optional ‘PC to
Inverter Connection Kit’ for both variants.
In addition the USS variant can also be connected via terminals 8 and 9 to a PC
using any RS485/232 interface converter.
Set P0719 = 55 or set the command source P0700 = 5 and the frequency setpoint
P1000 = 5 for complete inverter control when in STARTER mode.
Note
When downloading parameter sets associated with different firmware releases
using the STARTER tool, it should be noted that for the new parameters, the
default value is entered.
Summary of Contents for SINAMICS G110
Page 1: ...Operating Instructions Edition 04 2005 sinamics SINAMICS G110 ...
Page 10: ...Safety Instructions 04 2005 SINAMICS G110 Operating Instructions 10 6SL3298 0AA11 0BP0 ...
Page 14: ...Overview 04 2005 SINAMICS G110 Operating Instructions 14 6SL3298 0AA11 0BP0 ...
Page 72: ...Options 04 2005 SINAMICS G110 Operating Instructions 72 6SL3298 0AA11 0BP0 ...
Page 86: ...List of Abbreviations 04 2005 SINAMICS G110 Operating Instructions 86 6SL3298 0AA11 0BP0 ...
Page 90: ......
Page 91: ......