Commissioning 04/2005
SINAMICS G110 Operating Instructions
38
6SL3298-0AA11-0BP0
Changing parameters with the Basic Operator Panel
The description below serves as an example that shows how to change any
parameters using the BOP. These examples can also be used as a guide to
configuring the inverter for running via the BOP (start/stop commands and the
frequency setpoint are input on the BOP).
Changing P0003 – parameter access level
Step
Result on display
1
Press
to access parameters
2
Press
until P0003 is displayed
3
Press
to display the parameter value
4
Press
or
to set the required value
(set to 3)
5
Press
to confirm and store the value
6
All level 1 to level 3 parameters are now
visible to the user.
Changing P0719 an indexed parameter – setting BOP control
Step
Result on display
1
Press
to access parameters
2
Press
until P0719 is displayed
3
Press
to access the parameter value
4
Press
or
to select index 1
5
Press
to display actual set value
6
Press
or
to the required value
7
Press
to confirm and store the value
8
Press
until r0000 is displayed
9
Press
to return the display to the
standard drive display (as defined by the
customer)
Figure 3-5
Changing parameters via the BOP
Summary of Contents for SINAMICS G110
Page 1: ...Operating Instructions Edition 04 2005 sinamics SINAMICS G110 ...
Page 10: ...Safety Instructions 04 2005 SINAMICS G110 Operating Instructions 10 6SL3298 0AA11 0BP0 ...
Page 14: ...Overview 04 2005 SINAMICS G110 Operating Instructions 14 6SL3298 0AA11 0BP0 ...
Page 72: ...Options 04 2005 SINAMICS G110 Operating Instructions 72 6SL3298 0AA11 0BP0 ...
Page 86: ...List of Abbreviations 04 2005 SINAMICS G110 Operating Instructions 86 6SL3298 0AA11 0BP0 ...
Page 90: ......
Page 91: ......