04/2005 Commissioning
SINAMICS G110 Operating Instructions
6SL3298-0AA11-0BP0
31
3 Commissioning
This section describes the different methods of how to commission and run the
SINAMICS G110 inverter. A prerequisite is that the mechanical and electrical
installation has been completed as described in Section 2, starting on page 17 of
these Operating Instructions.
WARNING
¾
SINAMICS G110 inverters operate at high voltages.
¾
When operating electrical devices, it is impossible to avoid applying hazardous
voltages to certain parts of the equipment.
¾
Emergency Stop facilities according to EN 60204 IEC 204 (VDE 0113) must
remain operative in all operating modes of the control equipment. Any
disengagement of the Emergency Stop facility must not lead to uncontrolled or
undefined restart.
¾
Wherever faults occurring in the control equipment can lead to substantial
material damage or even grievous bodily injury (i.e. potentially dangerous
faults), additional external precautions must be taken or facilities provided to
ensure or enforce safe operation, even when a fault occurs (e.g. independent
limit switches, mechanical interlocks, etc.).
¾
Certain parameter settings may cause the inverter to restart automatically after
an input power failure.
¾
Motor parameters must be accurately configured for motor overload protection
to operate correctly above 5 Hz.
¾
This equipment is capable of providing internal motor overload protection in
accordance with UL508C. Refer to P0610 and P0335, I
2
t is ON by default.
¾
This equipment is suitable for use in a circuit capable of delivering not more
than 10,000 symmetrical amperes (rms), for a maximum voltage of 230 V, when
protected by an H or K type fuse, a circuit breaker or self-protected combination
motor controller.
¾
This equipment must not be used as an ‘emergency stop mechanism’ (see EN
60204, 9.2.5.4)
CAUTION
Only qualified personnel may enter settings in the control panels. Particular
attention must be paid to safety precautions and warnings at all times.
NOTES
¾
The inverter does not have a main power switch and is live when the mains
supply is connected. It waits, with the output disabled, until the RUN button is
pressed or for the presence of a digital ON signal at terminal 3.
¾
The inverter is designed to use control input signals to start and stop the motor.
Summary of Contents for SINAMICS G110
Page 1: ...Operating Instructions Edition 04 2005 sinamics SINAMICS G110 ...
Page 10: ...Safety Instructions 04 2005 SINAMICS G110 Operating Instructions 10 6SL3298 0AA11 0BP0 ...
Page 14: ...Overview 04 2005 SINAMICS G110 Operating Instructions 14 6SL3298 0AA11 0BP0 ...
Page 72: ...Options 04 2005 SINAMICS G110 Operating Instructions 72 6SL3298 0AA11 0BP0 ...
Page 86: ...List of Abbreviations 04 2005 SINAMICS G110 Operating Instructions 86 6SL3298 0AA11 0BP0 ...
Page 90: ......
Page 91: ......