Commissioning 04/2005
SINAMICS G110 Operating Instructions
48
6SL3298-0AA11-0BP0
Flow chart Quick Commissioning (Level 1 Only – P0003=1)
P1120
Ramp-Up Time
Acceptable Range: 0 - 650 s
Time taken for the motor to accelerate from standstill up to
maximum motor frequency.
P1121
Ramp-Down Time
Acceptable Range: 0 - 650 s
Time taken for motor to decelerate from maximum motor
frequency down to standstill
P1000
Selection of Frequency Setpoint
2
1 = BOP frequency control
2 = Analogue Setpoint (Analog variant only)
3 = Fixed frequencies
5 = USS Interface (USS variant only)
P0010
Start Quick Commissioning
0 = Ready to Run
1 = Quick Commissioning
(Recommended)
30 = Factory Setting
Note
Quick Commissioning must be started with P0010=1
and must be finished with P3900
≠
0. This ensures that
after quick commissioning P0010 will be set back to 0,
which is essential for motor operation.
P0100
Operation for Europe/N. America
0 = Power in kW;
f
default 50 Hz
1 = Power in hp;
f
default 60 Hz
2 = Power in kW;
f
default 60 Hz
Note
The position of the DIP switch (50/60 Hz) must be in
line with the setting of P0100 (0 or 1)
P0304
Rated Motor Voltage
1
Acceptable Range: 10 - 2000 V
Nominal motor voltage (V) from motor rating plate
P0305
Rated Motor Current
1
Acceptable Range: 0 - 2 x inverter rated current (A)
Nominal motor current (A) from motor rating plate
P0307
Rated Motor Power
1
Acceptable Range: 0.12 - 3.0 kW (0.16 - 4.02 hp)
Nominal motor power (kW) from motor rating plate.
If P0100 = 1, values will be in hp
P0310
Rated Motor Frequency
1
Acceptable Range: 12 - 650 Hz
Nominal motor frequency (Hz) from motor rating plate
P0311
Rated Motor Speed
1
Acceptable Range: 0 - 40000 min
-1
Nominal motor speed (rpm) from motor rating plate
P0700
Selection of Command Source
2
(on / off / reverse)
1 = Basic Operator Panel (BOP)
2 = Terminal / Digital Inputs
5 = USS Interface (USS variant only)
P1080
Min. Motor Frequency
Sets minimum motor frequency
(0-650Hz)
at which the
motor will run irrespective of the frequency setpoint. The
value set here is valid for both clockwise and anti-clockwise
rotation
P1082
Max. Motor Frequency
Sets maximum motor frequency
(0-650Hz)
at which the
motor will run at irrespective of the frequency setpoint. The
value set here is valid for both clockwise and anti-clockwise
rotation
1. Motor related parameters - please refer to the motor rating plate.
2. Denotes parameters that contain more detailed lists of possible settings for use in specific applications. Please refer to the
Parameter List.
P3900
End Quick Commissioning
0 = No Quick Commissioning (no motor calculation).
1 = End Quick Commissioning, with factory reset of all
other settings
(Recommended)
2 = End Quick Commissioning, with factory reset of I/O
settings.
3 = End Quick Commissioning, without reset of all other
settings.
Summary of Contents for SINAMICS G110
Page 1: ...Operating Instructions Edition 04 2005 sinamics SINAMICS G110 ...
Page 10: ...Safety Instructions 04 2005 SINAMICS G110 Operating Instructions 10 6SL3298 0AA11 0BP0 ...
Page 14: ...Overview 04 2005 SINAMICS G110 Operating Instructions 14 6SL3298 0AA11 0BP0 ...
Page 72: ...Options 04 2005 SINAMICS G110 Operating Instructions 72 6SL3298 0AA11 0BP0 ...
Page 86: ...List of Abbreviations 04 2005 SINAMICS G110 Operating Instructions 86 6SL3298 0AA11 0BP0 ...
Page 90: ......
Page 91: ......