Assembly of a CPU 41x–H
5.2 Monitoring functions of the CPU
S7-400H
54
System Manual, 03/2012, A5E00267695-11
Type of error
Cause of error
Response of the operating system
Error LED
Execution
canceled
The execution of a program block was
canceled. Possible reasons for the
cancellation are:
Nesting depth of nesting levels too great
Nesting depth of master control relay too
great
Nesting depth of synchronization errors
too great
Nesting depth of block call commands (U
stack) too great
Nesting depth of block call commands (B
stack) too great
Error during allocation of local data
Call of OB 88
If the OB is not loaded: CPU changes
to STOP mode.
INTF
Programming
error
User program error:
BCD conversion error
Range length error
Range error
Alignment error
Write error
Timer number error
Counter number error
Block number error
Block not loaded
Call of OB 121
If the OB is not loaded: CPU changes
to STOP mode.
INTF
MC7 code error
Error in the compiled user program, for
example, illegal OP code or a jump beyond
block end
CPU changes to STOP mode.
Restart or memory reset required.
INTF