Technical data
20.4 Technical specifications of the CPU 417–5H PN/DP; (6ES7 417-5HK06–0AB0)
S7-400H
System Manual, 03/2012, A5E00267695-11
425
Functionality
MPI
Yes
PROFIBUS DP
DP master
1st interface in MPI mode
Utilities
PG/OP communication
Yes
Routing
Yes
S7 communication
Yes
Global data communication
No
S7 basic communication
No
Transmission rates
Maximum 12 Mbps
1st interface in DP master mode
Utilities
PG/OP communication
Yes
Routing
Yes
S7 communication
Yes
Global data communication
No
S7 basic communication
No
Constant bus cycle time
No
SYNC/FREEZE
No
Enable/disable DP slaves
No
Direct data exchange (cross-traffic)
No
Transmission rates
Maximum 12 Mbps
Number of DP slaves
Maximum 32
Number of slots per interface
Maximum 544
Address range
Maximum 2 KB inputs / 2 KB outputs
User data per DP slave
Maximum 244 bytes
Maximum 244 bytes inputs,
Maximum 244 bytes outputs,
Maximum 244 slots
Maximum 128 bytes per slot
Note:
The total of input bytes across all slots may not exceed 244.
The total of output bytes across all slots may not exceed 244.
The address range of the interface (maximum 2 KB inputs / 2 KB outputs) must not be exceeded
in total across all 32 slaves.