Technical data
20.4 Technical specifications of the CPU 417–5H PN/DP; (6ES7 417-5HK06–0AB0)
S7-400H
430
System Manual, 03/2012, A5E00267695-11
Voltages and currents
Current consumption from S7–400 bus (5 V DC) Typ. 1.6 A
Max. 1.9 A
Current consumption from S7-400 bus (24 V DC)
The CPU does not consume any current at 24 V,
it only makes this voltage available on the
MPI/DP interface.
Total current consumption of the components
connected to the MPI/DP interfaces, but
maximum 150 mA per interface
Current output to DP interface (5 V DC)
Max. 90 mA
Backup current
Typically 180 µA (up to 40 °C)
Maximum 1000 µA
Maximum backup time
See Module Specifications Reference Manual,
Section 3.3.
Feed of external backup voltage to the CPU
5 V DC to 15 V DC
Power loss
Typ. 7.5 W