S7-400 cycle and response times
19.5 Response time
S7-400H
374
System Manual, 03/2012, A5E00267695-11
Table 19- 11 Direct access of the CPUs to I/O modules in the expansion unit with local link
Access mode
412-5H
stand-
alone
mode
412-5H
redundant
414–5H
stand-
alone
mode
414–5H
redundant
416-5H
stand-
alone
mode
416-5H
redundant
417–5H
stand-
alone
mode
417–5H
redundant
Read byte
Read word
Read double
word
Write byte
Write word
Write double
word
6.0 µs
11.0 µs
20.0 µs
5.3 µs
10.6 µs
19.8 µs
36.0 µs
41.3 µs
49.0 µs
35.3 µs
41.3 µs
49.0 µs
5.6 µs
10.5 µs
19.9 µs
5.3 µs
10.2 µs
19.8 µs
24.5 µs
32.1 µs
40.0 µs
24.5 µs
28.6 µs
39.8 µs
5.6 µs
10.5 µs
19.9 µs
5.3 µs
10.2 µs
19.8 µs
16.1 µs
23.8 µs
31.7 µs
16.1 µs
21.5 µs
31.5 µs
5.6 µs
10.5 µs
19.9 µs
5.3 µs
10.2 µs
19.8 µs
13.4 µs
18.6 µs
28.7 µs
13.4 µs
18.3 µs
28.0 µs
Table 19- 12 Direct access of the CPUs to I/O modules in the expansion unit with remote link, setting 100 m
Access mode
412-5H
stand-
alone
mode
412-5H
redundant
414–5H
stand-
alone
mode
414–5H
redundant
416-5H
stand-
alone
mode
416-5H
redundant
417–5H
Einzel-
betrieb
417–5H
redundant
Read byte
Read word
Read double
word
Write byte
Write word
Write double
word
11.5 µs
23.0 µs
46.0 µs
11.0 µs
22.0 µs
44.5 µs
41.3 µs
49.0 µs
72.1 µs
41.3 µs
49.0 µs
72.1 µs
11.5 µs
23.0 µs
46.0 µs
11.0 µs
22.0 µs
44.5 µs
27.5 µs
39.8 µs
62.9 µs
27.0 µs
39.8 µs
62.9 µs
11.4 µs
22.8 µs
45.9 µs
10.8 µs
21.9 µs
44.0 µs
20.3 µs
31.5 µs
54.5 µs
20.2 µs
31.5 µs
54.5 µs
11.3 µs
22.8 µs
45.9 µs
10.8 µs
21.9 µs
44.0 µs
17.0 µs
28.6 µs
51.7 µs
16.8 µs
27.8 µs
50.0 ms
Note
You can also achieve fast response times by using hardware interrupts; see section Interrupt