Technical data
20.2 Technical specifications of the CPU 414–5H PN/DP; (6ES7 414-5HM06–0AB0)
S7-400H
400
System Manual, 03/2012, A5E00267695-11
Open IE communication over TCP/IP
Number of connections / access points, total
Maximum 62
Possible port numbers
1 to 49151
Where parameters are assigned without specification of a port number, the system assigns a port
from the dynamic port number range between 49152 and 65534
Reserved port numbers
0 reserved
TCP 20, 21 FTP
TCP 25 SMTP
TCP 102 RFC1006
UDP 135 RPC-DCOM
UDP 161 SNMP_REQUEST
UDP 34962 PN IO
UDP 34963 PN IO
UDP 34964 PN IO
UDP 65532 NTP
UDP 65533 NTP
UDP 65534 NTP
UDP 65535 NTP
TCP/IP
Yes, via integrated PROFINET interface and
loadable FBs
Maximum number of connections
62
Data length, max.
32767 bytes
ISO-on-TCP
Yes (via integrated PROFINET interface or CP
443-1/ EX20/GX 20 and loadable FBs)
Maximum number of connections
62
Maximum data length via integrated
PROFINET interface
32767 bytes
Maximum data length via CP 443-1
1452 bytes
UDP
Yes, via integrated PROFINET interface and
loadable blocks
Maximum number of connections
62
Data length, max.
1472 bytes
Interfaces
You may not configure the CPU as DP slave
1st interface
Interface designation
X1
Type of interface
integrated
Physics
RS 485/Profibus
Electrically isolated
Yes
Power supply to interface (15 V DC to 30 V DC)
Max. 150 mA
Number of connection resources
MPI: 32, DP: 16
If a diagnostic repeater is used on the segment,
the number of connection resources on the
segment is reduced by 1