5.8.7
Technical Specifications of
the Interface Submodules
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to
Standard C 22.2 No. 142, Report LR 63533
Type of protection
IP 00
Ambient temperature
in operation
for transporation and storage
0 to +55
o
C
- 40 to +70
o
C
Relative humidity
95 % max. at 25
o
C
no condensation
Supply voltage
5V
±
5%
24V + 25%/- 17%
Transmission rate
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule
9600 bit/s fixed
19200 bit/s max.
9600 bit/s max.
19200 bit/s max. (when
submodule is used in a CPU)
9600 bit/s fixed
Front connector, female
PG, RS422 A/485, SINEC L1
submodule
V.24, TTY submodule
15-pin Cannon
25-pin Cannon
Transmission cable
Shielded four-wire line (five-wire
line for RS422 A) with braided
shield and metal housing on
connector, grounding required at
both ends.
Line length
PG submodule
V.24 submodule
TTYsubmodule
RS422 A/485 submodule
SINEC L1 submodule
1000 m max.
16 m max.
1000 m max.
1200 m max.
1000 m max.
5
Interface Submodule
System Manual
C79000-B8576-C199-03
5 - 95