Inputs
Inputs of the load power supply are given in the following table:
Inputs
Current Inputs Description
L1
N
PE
120V/240V,
50Hz
Phase
Neutral conductor
Protective conductor
4 inhibit inputs
(2L+ to 5L+)
2.5 mA
Outputs 2L+ to 5L+ can be
switched off individually with a
logic low at these inputs.
Indicators
Given in the following table are the indicators of the load power
supply and their significance:
Indicators
Significance
5 green LEDs
Outputs 1L+ to 5L+ are operating correctly
1 red LED
Short-circuit at outputs 2L+ to 5L+
Controls
The voltage selector switch is on the basic module and is set to 230 V
when delivered (see switch labelling).
Front connector
Signal lines for the load power supply module must be connected via
a front connector. The front connector is not supplied with the power
supply module and must be ordered separately. You have a choice of
crimp connections and screw connections. The order numbers can be
found in the ordering information.
The front connector hooks into the lower end of the module; it should
be swivelled up and screwed to the module.
4
24 V/4 A Load Power Supply
System Manual
C79000-B8576-C199-03
4 - 63