8.4.12
6ES5 454-4UA13 Digital
Output Module
Rated supply voltage L+
24 V DC
Number of outputs
16, short-circuit protected
1)
Isolation
Yes, 1 group of 16 outputs
Range for supply voltage
20 to 30 V DC
Fusing
6.3 A slow, 1 fuse per 4 outputs
Output voltage
for logic 1
for logic 0
L + - 2 V min.
3 V max.
Switching current (resistive, inductive load)
10 mA to 2 A
2)
Residual current at logic 0
1 mA max.
Switching current for lamps
0.45 A max. (10 W)
Switching frequency with resistive load
with inductive load
100 Hz max.
0.2 Hz max. at 1 A, 0.1 Hz at 2 A
Breaking voltage (inductive)
Limited to L+ - 47 V
Total switching current
4 A max. per 4 outputs
Coincidence factor (total load capability)
50 %
Permissible line length
400 m max. unshielded
Power supply
Digital section from system bus
5 V, 100 mA typical
Current consumption from L+/L-
24 V, 100 mA typical
Power dissipation (rated operation)
17.5 W
Enable input (F+/F-)
Rated input voltage
24 V DC
Input voltage for logic 1
for logic 0
13 to 33 V
- 33 to 5 V
Rated input current
5 mA
Permissible line length
200 m max.
Short-circuit monitoring
Indicator for signalling output (H+)
Red LED for 4 outputs
Output voltage referred to L-
(with feed at 1L+)
for logic 1
for logic 0
1L+ - 5 V min.
3 V max.
Switching current
10 mA max., limited
Voltage test to VDE 0160
Between two groups: 1250 V AC
Between group and ground point: 1250 V AC
Mechanical specifications
Dimensions (W x H x D)
40 mm x 255 mm x 195 mm
Weight
Approx. 0.55 kg
1) Short-circuit protection responds with line resistance
≤
4.75 ohms
2) One digital input is permissible as minimum load.
8
Specification Sheets for the Modules
System Manual
C79000-B8576-C199-03
8 - 57