5
Using the Command Interface
69
CP 343−2 / CP 343−2 P AS−Interface Master
Release 08/2008
C79000−G8976−C149−04
5.2.8
Store_Actual_Configuration
Purpose of the Command
With this call, the (actual) configuration data (I/O configuration, ID code, extended
ID1 code and extended ID2 code) of all AS-i slaves are stored permanently in the
EEPROM as the (expected) configuration data. The list of activated AS-i slaves
(LAS) is adopted in the list of permanent AS-i slaves (LPS).
When this command is executed, the AS-i master changes to the of fline phase and
then changes back to the normal mode (warm restart on the AS-i master).
The call is
not
executed in the protected mode.
Notice
If you configure the AS-i slaves with HW Config, using the call described here is
generally unnecessary
If you do use the call, you will overwrite the corresponding configuration data
originating from the button configuration or the configuration set with HW Config.
Structure of the Job Data in the Send Buffer
Byte
Meaning
0
Command number: 07
H