5
Using the Command Interface
68
CP 343−2 / CP 343−2 P AS−Interface Master
Release 08/2008
C79000−G8976−C149−04
5.2.7
Get_Extended_Permanent_Configuration
Meaning
This call reads the following configuration data (configured data) of an addressed
AS-i slave stored on the EEPROM of the AS-i master.
S
I/O configuration
S
ID code
S
Extended ID1 code
S
Extended ID2 code
The configuration data are specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the Job Data in the Send Buffer
Byte
Meaning
0
Command number 26
H
1
Slave address
Structure of the Response Data in the Receive Buffer
Byte
Meaning
Bit 7
Bit 4
Bit 3
Bit 0
0
ID code
I/O configuration
1
Extended ID1 code
Extended ID2 code
2
0
3
0